Written by Joanne Mulloy, Acoustic Solutions Specialist & Technical Reviewer
Reviewed by Joe Sutcliffe, Managing Director & Lead Acoustic Surveyor
Presentation Spaces Ltd ·
A glazed notice board is a notice board with a transparent cover, usually glass or polycarbonate, fitted over the display surface. In schools, BB 100 says boards in dead end corridors should be covered, and boards in a protected corridor should have a cover, preferably top hung.[1]
Key points
- BB 100 says notice boards should not be provided in dead end corridors unless covered by a suitable material, for example glass or polycarbonate.[1]
- It also says notice boards in a protected corridor should be fitted with a cover, preferably top hung so that the cover cannot be left jutting out into the escape route.[1]
- BB 100 dates from March 2014, so the current Approved Document B should be read with it.[1][2]
- A cover changes what a fire assessor looks at: the guidance treats the surface of glazing as part of a wall lining, except glazing in doors.[2]
How it works
The cover sits in front of the surface that holds the notices. BB 100 groups the cover requirement with its guidance on corridors and circulation areas, where it says notice boards should be no more than 3 m wide with a gap of at least 1 m between boards on the same wall.[1] A top-hung cover is its preferred arrangement for protected corridors, because the cover cannot then be left open into the route.[1]
A glazed cover does not remove the need to look at what sits behind it. BB 100 permits boards "with a surface spread of flame" in classrooms and limits their run, and the board surface behind the glass is still the display material.[1]
The numbers
- Corridors: boards not more than 3 m wide, with at least 1 m between boards on the same wall.[1]
- Classrooms: boards not more than 2.5 m long without a break of at least 0.4 m.[1]
- Walls: Approved Document B counts the internal surface of internal and external glazing, except glazing in doors, as a wall for lining purposes. Lining classes are D-s3, d2 in small rooms up to 30 m2 in non-residential buildings, C-s3, d2 in other rooms and B-s3, d2 in other circulation spaces.[2]
This page does not state a fire class for glass or polycarbonate covers. The classification belongs to the specific product tested under BS EN 13501-1, which is paywalled and not reproduced here.[3]
In schools and SEN settings
BB 100 covers special schools and pupil referral units, and sets no separate rule for SEN settings.[1] Whether a cover is glass or polycarbonate, and who may open it, are decisions for the school's risk assessment. Security and safeguarding questions about locks are covered under lockable notice board.
How to choose
- Ask which corridor type the board is going in. The cover rule in BB 100 is specific to dead end and protected corridors.[1]
- Ask for the cover material and its test evidence, with the full European class and how the sample was fixed.[3]
- Ask how the cover opens. BB 100 prefers top-hung covers in protected corridors.[1]
What people get wrong
- Treating glass as exempt. Approved Document B counts the surface of glazing in its definition of a wall, except in doors.[2]
- Assuming the cover rule applies everywhere. It is stated for dead end corridors and protected corridors.[1]
- Reading a 2014 bulletin as the whole picture. The 2025 amendments to Approved Document B changed how classes are given.[2]
FAQ
Does a notice board in a school corridor have to be glazed?
BB 100 asks for a cover in dead end corridors and in protected corridors, with a preference for top hung covers in the latter.[1] Other corridors and rooms are covered by the 3 m and 2.5 m limits.[1]
Is polycarbonate acceptable as a cover?
BB 100 names glass or polycarbonate as examples of a suitable material for dead end corridors.[1]
Is a glazed board the same as a lockable board?
No. Glazed describes a cover, and lockable describes access. A board can be either, both or neither. See notice board.
Related terms
- Notice board
- Lockable notice board
- Building Bulletin 100
- Surface spread of flame
- Tamperproof notice board
See it in our range
Notice boards: ask for the cover material, how it opens and the test evidence for the exact board.
Sources
- Design for fire safety in schools: BB 100. Department for Education (GOV.UK), March 2014. Accessed November 2026.
- Approved Document B (fire safety) volume 2: Buildings other than dwellings, 2019 edition incorporating 2020, 2022, 2025 and 2026 amendments collated with 2029 amendments. Ministry of Housing, Communities and Local Government (GOV.UK), GOV.UK page last updated 16 September 2026. Accessed November 2026.
- BS EN 13501-1:2018 Fire classification of construction products and building elements: Classification using data from reaction to fire tests. BSI Knowledge, published 31 January 2019. Accessed November 2026.