Surface spread of flame is how quickly flame travels across the surface of a wall or ceiling lining. Fire guidance limits it so that linings do not feed fire growth. Under the national system it was graded Class 0 to 4 using BS 476-7, now withdrawn; English guidance now uses European classes.[1][2][3]
Key points
- BB100, the DfE's fire safety design guide for schools, meets the lining requirement by giving linings a low rate of surface spread of flame.[1]
- The national grades were Class 1 to 4 under BS 476-7, with Class 1 the highest. Class 0 was a building-guidance grade, not a class in any British Standard test.[1]
- BSI lists BS 476-7:1997 as withdrawn on 4 March 2025.[2]
- Approved Document B removed its national classifications for reaction to fire in amendments that took effect on 2 March 2025.[3]
How it works
BB100 says linings are rated for surface spread of flame by reference to BS 476-7, and that products are classified 1, 2, 3 or 4. Class 0 is the top grade for lining materials. A material reaches it if it is composed throughout of materials of limited combustibility, or is a Class 1 material with a fire propagation index of no more than 12 and a sub-index of no more than 6.[1]
The European system replaces this with the classes in EN 13501-1. The two scales are not interchangeable: BB100 says a product cannot usually assume a European class unless it was tested for it.[1]
The numbers
BB100 table 7, published in 2014, set linings out in both systems.[1]
- Small rooms of up to 30 m2: national Class 3, European D-s3, d2.[1]
- Other rooms: national Class 1, European C-s3, d2.[1]
- Other circulation spaces: national Class 0, European B-s3, d2.[1]
Approved Document B volume 2 now carries the European column only, with the same three classes.[4]
What changed in 2025
The 2025 amendments to Approved Document B deleted the section on national classifications for reaction to fire and the index entries for BS 476-3, BS 476-6 and BS 476-7.[3] Work already under way is not caught: the earlier edition continues where a building notice, initial notice or full plans application was made before 2 March 2025 and the work was started and sufficiently progressed before that date or within six months of it.[3]
In schools and SEN settings
BB100 gives specific advice on notice boards. Boards with a surface spread of flame rating are permitted in classrooms, but should not run more than 2.5 m without a break of at least 0.4 m, and should be away from sources of ignition.[1] Boards should not be provided in dead end corridors unless covered, for example by glass or polycarbonate.[1] A separate passage on corridors says boards should not be more than 3 m wide, with a gap of at least 1 m between boards on one wall, and a cover on boards in a protected corridor.[1] BB100 dates from 2014, so confirm the current requirement with the school's fire risk assessment.
What people get wrong
- Calling Class 0 a British Standard class. BB100 says it is not identified in any British Standard test.[1]
- Offering BS 476-7 evidence as current. The standard is withdrawn.[2]
- Assuming one rating suits every board. Small differences in thickness, substrate, fixings or colour may change the rating.[1]
FAQ
What is the difference between Class 0 and Class 1?
Class 0 is the higher grade. In BB100, circulation spaces were Class 0 and other rooms Class 1.[1] See Class 0 fire rating and Class 1 surface spread of flame.
Is BS 476-7 still valid?
BSI lists BS 476-7:1997 as withdrawn from 4 March 2025.[2] See BS 476 Part 7.
Which rating should a school notice board have?
BB100 and Approved Document B state the lining classes in the table above, but a school's own fire risk assessment decides how they apply to a given board.[1][4] See fire retardant notice board.
Related terms
- EN 13501-1
- Class 0 fire rating
- Class 1 surface spread of flame
- BS 476 Part 7
- Fire safety in schools (BB 100)
- Fire retardant notice board
See it in our range
Notice boards, including Class 1 and Class B fire retardant felt boards: ask for the test evidence for the exact board before specifying it.
Sources
- Design for fire safety in schools: BB 100. Department for Education (GOV.UK), March 2014. Accessed November 2026.
- BS 476-7:1997 Fire tests on building materials and structures: Method of test to determine the classification of the surface spread of flame of products. BSI Knowledge, published 15 January 1997, withdrawn 4 March 2025. Accessed November 2026.
- Amendments to Approved Document B, volumes 1 and 2 (2025 amendments, taking effect on 2 March 2025). Ministry of Housing, Communities and Local Government (GOV.UK), published September 2024. Accessed November 2026.
- Approved Document B (fire safety) volume 2: Buildings other than dwellings, 2019 edition incorporating 2020, 2022, 2025 and 2026 amendments collated with 2029 amendments. Ministry of Housing, Communities and Local Government (GOV.UK), GOV.UK page last updated 16 September 2026. Accessed November 2026.